Thermal energy meter MV 311

Thermal energy meter, MI-004 2014/32/EU approval

Description

The MV311 thermal energy meter is designed for the thermal balance or the billing of the thermal energy produced, according to the EN1434 standard and the MI-004 2014/32/EU approval. The MI-004 approval requires factory programming of the main parameters. Equipped with two types of meter inputs, it can be connected to mechanical meters, electromagnetic flow meters, ultrasonic flow meters. Its sensor power supply can power the MV800 or CS3795 type flow meters that we can offer.

It has pulse or 4-20 mA inputs for flow measurement and Pt 100/500/1000 temperature inputs.

Technical characteristics

Fluid: water or water + Glycol (60% max)
Thermal power: Ps max = 99999 GW
Unit of measurement: kW/MJ
Power supply: 100…240 V AC / 50 Hz (Option: 24 to 36 V AC/DC, 12 to 48 V DC or 12 to 48 V DC PoE), optional rechargeable backup battery (1 month of autonomy without external power supply, I/O = Off),
Maximum consumption: 6 W – 8 VA
Measuring device power supply (flow meter): 24 V DC max 100 mA
Ambient temperature: +5 to +55 °C
PC/ABS plastic housing – IP 65
Dimensions: H 179 x W 125 x Th 68 mm (Open: Th 104 mm)
Mounting: DIN rail or wall-mounted
Graphic display: 122 x 32, backlit
6-language menu (FR / UK / DE / ES / IT / NL)
Programming by 3 keys on the front, by PC (MCP software)
Measuring input: analog 0/4-20 mA, or pulse (0.003 Hz to 1 kHz) programmable
Pulse inputs 3 inputs (0.003 Hz to 1 kHz) for water meters or other fluids
Temperature inputs 2 inputs (forward/return)
Pt 100 temperature probes, 4 wires (Option: Pt 500, Pt 1000)
Temperature scale: ϑ min -15 °C, ϑ max 200 °C (150 °C for MID)
Delta T Δϑ min 0.1 °C (2 °C for MID), Δϑ max 150 °C (150 °C for MID)
System accuracy: ± 0.20% (0.18 + Δϑ mini/Δϑ)
Analog output 0/4-20mA (flow, power, T1, T2 or ΔT)
Digital outputs 2 programmable outputs volume and energy
Reversibility Hot / Cold Automatic or on external pulse
Protocols (Options) RS 485 (Mbus, MODBus MS/TP, BACNet MS/TP), Ethernet (Modbus IP, BACneT IP)
Recorder (Option) 4 GB (minimum recording rate: 1 second)
Certification (option) MID MI-004 2014/32/EU