3 in 1 Universal Analog Input Module W-M1B103/104

8 or 16 universal analog inputs voltage, current and thermocouple module with RS485 Modbus communication

Categories: ,

Description

These modules have 8 and 16 channels voltage / current / thermocouple analog input with high common mode voltage protection.

Features

  • Voltage Range ±100mV, ±500mV, ±1V, ±5V, ±10V, 0-100mV, 0-500mV, 0-1V, 0-5V, 0-10V
  • Current Range ± 20 mA, 4-20 mA, 0-20 mA (Slide Switch Select)
  • Direct Sensor Input J, K, T, E, R, S, B, N
  • Burn-out Detection Yes (all V, 4 ~ 20 mA & all T/C)
  • Sampling Rates 12 Samples / Second (Total)
  • Resolution 16-bit
  • Accuracy ± 0.1% FSR
  • Input Impedance Voltage: 2MΩ, Current: 120 Ω
  • Span Drift ± 25 ppm/ºC
  • Zero Drift ± 6 μV/ºC
  • Input Voltage Protection ± 240V for Voltage Mode (Exclude ± 100 mV, 0-100 mV)
  • Common Mode Voltage 240 V
  • Channel Independent configuration: Yes
  • Interface RS-485
  • Power Consumption 1.6W @ 24 VDC (W-M1B103) 2.8W @ 24 VDC (W-M1B104)
  • Power Requirement 10 ~ 60 VDC
  • Watchdog Timer System (1.6 Second Fixed)
  • Intra-Module Isolation, Field-to Logic: 2500 VDC
  • Protocol Modbus RTU
  • Speed From 1200-115.2k bps
  • Distance 1.2 km at 9.6 kbps
  • Operating Temp.-25 ~ 70 ºC
  • Storage Temp.-30 ~ 75°C
  • Operating Humidity 10% to 90% (non-condensing)
  • LED Indicators PWR, Comm, Program, Status
  • Weight 65g (Average)
  • Dimensions 472 x 121 x 120mm
  • W-M1B103 8 universal analog inputs module (voltage / current / thermocouple)
  • W-M1B104 16 universal analog inputs module (voltage / current / thermocouple)